Greenhouse heating calculator
Structure, glazing and temperatures → heater output, summer CFM and energy cost.
Open full calculator · Calculation schema v2 · Sources checked 2026-10-28
Formula and worked example
Conduction: Q = U × envelope area × ΔT. Example: 100 m² × 3 W/m²K × 20 K = 6,000 W conduction only, before air exchange or other losses.
Air exchange: Q = 1.2 kg/m³ × 1,005 J/kgK × ACH × air volume × ΔT ÷ 3,600. Thermal output is conduction plus air exchange. Input kW = output kW ÷ efficiency. Cost = input kW × equivalent full-load hours × tariff. 1 W = 3.41214 BTU/hr; 1 imperial U = 5.67826 W/m²K.
The selected sizing margin (15% by default) is shown separately from the modeled operating cost. Solar gains, ground losses, changing weather and thermal bridges are not included. This estimate does not size wiring or certify heater suitability.
U-values: Palram twin-wall panel data (4/6/8/10 mm: 3.8/3.5/3.3/2.9 W/m²K); Texas A&M glazing and air-exchange estimates (single/double film: 1.15/0.70; single/double glass: 1.13/0.65 imperial U). Glass estimates are generic glazing values, not product-specific tempered-glass certification. Use the supplier’s whole-system U-value when available.
UMass natural ventilation guidance: combined sidewall openings and combined ridge openings should each be 15–20% of floor area. These are opening references, not a guaranteed flow. Ventilation alone cannot cool below outdoor dry-bulb temperature.
Read the winter greenhouse heating guide or open the standalone heating calculator.